FLEX Ex 85…250V ac In/Quad-Ex dc Out Power Supply 13

Publication

1797-5.34 - September 2011



The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a
system when the approved values of V

oc

and I

sc

of the associated apparatus are

less than or equal to V

max

and I

max

of the intrinsically safe apparatus and the

approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+

C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.



Wiring methods must be in accordance with the NEC, ANSI/NFPA 70,

Article 504 or the CEC CSA C22.1, Part 1, Appendix F. For additional
information refer to ANSI/ISA RP12.6.



Wiring methods must be in accordance with the NEC, ANSI/NFPA 70,

Article 501 or the CEC CSA C22.1, Part 1, Section 18.

1 and 2

Any one

channel (for

example, ch1)

11(+), 10(-)

9.5

1.0

A, B, IIC

0.5

8

C, E, IIB

1.5

32

D, F, G, IIA

4.0

64

11

11

Nonhazardous
Location

V ac To Next Power
Supply 1797-PS1N

Input
Power

Nonintrinsically
Safe Wiring

Intrinsically Safe
Wiring

To any IS device
with entity
concept
parameters  of
(V

max

, I

max

, C

i

, L

i

)

appropriate for
connection to
associated
apparatus with
entity concept
parameters listed
in Table 4.

43307

Hazardous (Classified)

Location

1797-PS1N

Class I, Division 1, Groups

 

 

