Customer connections – Rockwell Automation 1797-PS1N FLEX Ex 85-250V AC In/Quad-Ex DC Out Power Supply User Manual

Page 8

Advertising
background image

8 FLEX Ex 85…250V ac In/Quad-Ex dc Out Power Supply

Publication

1797-5.34 - September 2011

5. Connect the hazardous incoming power wiring to the input terminals

making sure all connections are tight.

You can daisy chain the hazardous incoming power wiring to further
supplies to simplify system wiring.

6. Pour the seals and inspect them, as necessary.

7. Screw the lid back into place until tight.

8. Lock the lid by screwing the small set screw located in the bump on

the circumference of the lid.

The set screw prevents the lid from rotating more than half a turn.

Customer Connections

ATTENTION

Keep hazardous and IS-safe wiring separated in a suitable fashion.
Do not leave long, excess wiring that could bridge between
hazardous and safe areas as the power supply is closed.

Vin

Vout

Chassis
GND

IS Isolation

Hazardous to

IS

-V
+V Out 1

-V

+V

Out 2

-V

+V Out 3

41315

IS Limiters

Voltage and Current

-V
+V

Out 4

ac

Type of Power Input

IS Power Output

Advertising