Hazardous area, Safe area – Rockwell Automation 1797-PS1N FLEX Ex 85-250V AC In/Quad-Ex DC Out Power Supply User Manual
Page 5

FLEX Ex 85…250V ac In/Quad-Ex dc Out Power Supply 5
Publication
1797-5.34 - September 2011
Make certain that you only connect intrinsically-safe power supplies to other
intrinsically-safe system modules or adapters to maintain the integrity of the
intrinsically-safe backplane.
IMPORTANT
Even though modules may be supplied with power from the same
power supply output channel, galvanic isolation in the module
provides module-to-module galvanic isolation. Depending upon the
module type, galvanic isolation (channel-to-channel within the
module) may or may not be provided. See the module’s
specifications for more information.
IS Pwr
Safe Area
Hazardous Area
1797 power supply
1797 power supply
1797 power supply
ACNR Spare
IE8
OE8
IRT8
Spare Spare
IJ2
IJ2
ACNR OB4
OB4D
IBN16 IBN16 IBN16
IE8
IRT8
OE8
RPA
RPFM
RPFM
IS 1797 I/O
IS 1797 I/O
IS 1797 Fiber Hub
IS Pwr
IS Pwr
IS Pwr
IS Pwr
IS Pwr
IS Pwr
IS Pwr
IS Pwr
IS Pwr
IS Pwr
IS Pwr
43475
Unsafe
Power
Entrance
Spare
Unsafe
Power
Entrance
Unsafe
Power
Entrance
41307