For mounting of the power supply, conduit runs must have sealing

fittings connected within 6 in. of enclosure.



The wiring contained within the nonintrinsically-safe wiring

compartment and the intrinsically-safe wiring compartment shall be separated
from each other. Care must be taken to guarantee the separation of
nonintrinsically-safe and intrinsically-safe wiring. The partitions within the
power supply provide the necessary isolation for the electronics and the
wiring, however, extreme care must be taken to guarantee wires are contained
within their appropriate compartment and cannot contact any of the
electronics.



WARNING: Substitution of components may impair intrinsic safety.

AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.



Cable must be rated at a minimum of 100

o

C (212 °F).



Warning: Keep cover tightly closed when circuits are alive.



After disconnecting power supply, wait 15 minutes before removing

cover.



No live maintenance.

The ambient operating temperature (T

amb

) for this system

is -20…70

o

C.