FLEX Ex 85…250V ac In/Quad-Ex dc Out Power Supply 15

Publication

1797-5.34 - September 2011

FM I/O Entity Parameters

If this product has the FM mark, it has been designed, evaluated, tested, and
certified to meet the following standards:

• FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous

(Classified) Locations General Requirements

• FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated

Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified)
Locations

• FM C1. No.3615:1989, Explosionproof Electrical Equipment General

Requirements

• FM C1. No.3810:1989, 1995, Electrical and Electronic Test,

Measuring and Process Control Equipment

• ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC).

FM I/O Entity Parameters for 1797-PS1N

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(A)

Groups

C

a

(

µF)

L

a

(

µH)

1 and 2

Any one

channel

(for

example,

ch1)

11(+), 10(-)

9.5

1.0

A, B, IIC

0.5

8

C, E, IIB

1.5

32

D, F, G, IIA

4.0

64