Drive grounding, Power wiring, Drive grounding -5 power wiring -5 – Rockwell Automation 1395 Digital DC Drive User Manual
Page 59
Publication 2361-5.01 July 1998
Installing Your Drive
Drive Grounding
The internal drive components should already be connected to the
ground (PE) and zero potential (TE) buses. Connect any additional
items to PE and TE (motor, encoder, etc.) as necessary, and connect
the PE and TE buses to ground as explained in publication 1395-5.40.
Power Wiring
Table 5.D: Standard Field Voltage Output
Table 5.E: Motor Connections for CCW Rotation
AC Incoming Voltage
To Drive (V AC)
DC Supply Output
Voltage To Field (V DC)
460
300
575
300
660
300
Connection
Drive
Drive Terminal
Connection
Motor Lead
Motor Field
1250, 1650, 3000A
TB7-1
TB7-3
F1 (+)
F2 (-)
Motor Armature
1250, 1650, 3000A
A1
A2
A1 (+)
A2 (-)
!
ATTENTION: The motor field supply is phase
sensitive. To guard against possible drive or motor
damage, ensure that the connections comply to
Figure 5.2.