Installing Your Drive

5-5

Drive Grounding

The internal drive components should already be connected to the
ground (PE) and zero potential (TE) buses. Connect any additional
items to PE and TE (motor, encoder, etc.) as necessary, and connect
the PE and TE buses to ground as explained in publication 1395-5.40.

Power Wiring

Table 5.D: Standard Field Voltage Output

Table 5.E: Motor Connections for CCW Rotation

AC Incoming Voltage

To Drive (V AC)

DC Supply Output

Voltage To Field (V DC)

460

300

575

300

660

300

Connection

Drive

Drive Terminal
Connection

Motor Lead

Motor Field

1250, 1650, 3000A

TB7-1
TB7-3

F1 (+)
F2 (-)

Motor Armature

1250, 1650, 3000A

A1
A2

A1 (+)
A2 (-)

!

ATTENTION: The motor field supply is phase
sensitive. To guard against possible drive or motor
damage, ensure that the connections comply to
Figure 5.2.