Commissioning
Chapter 3
Simulate Warnings and Faults
This section describes how to simulate warnings and faults, and how to clear or
reset the alarm. Warning codes begin with a W prefix, and fault codes begin with
a F prefix.
The Set Frequency: field will already have 50 Hz shown from the previous
exercise in the Set Freq: dialog box.
1.
Press ,
and
press
in
the
Start Drive?
dialog box.
Simulate the Transformer Overtemperature Warning
1.
Open the LV door of the Isolation Transformer cabinet.
2.
Using a jumper wire, connect terminal blocks 401 and 419 on the
transformer protection relay.
Alarm
Self-clearing
Requires Reset
Transformer Overtemperature Warning
YES
Transformer Overtemperature Trip
YES
Transformer Cabinet Main Cooling Fan Fault
YES
Power Module Cabinet Main Cooling Fan Fault
YES
Cabinet Door Open Warning
– Left Isolation Transformer Cabinet Door
– Right Isolation Transformer Cabinet Door
– Left Power Module/LV Cabinet Door
– Right Power Module/LV Cabinet Door
– Bypass Cabinet Door (if applicable)
YES