Parameters t11...t13 – Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Commissioning Manual User Manual
Page 71

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
71
No-load Test
Chapter 4
Parameters T11...T13
To change Parameter T11:
1.
Press the T11 Parameter input field.
T08
Remote Frequency Command Selection
1: Analog
2: 4-Step Speed
4: Communication Port
1
ON
1
4
Setup
Confirm P262=1
If T8=1, then the analog quantity 4...20 mA from Remote,
4 mA corresponds to 0 Hz, 20 mA corresponds to the rated
frequency.
If T8=2, use T13 to set step speed
If T8=4, communication mode with remote
T09
Frequency Step For Accel or Decel
1
ON
1
Rated
Frequency
Setup
Changes the step frequency when Accel or Decel is pressed
T10
Exit Config Environment Password
555
OFF
Setup
This function will not work if the drive is running.
T11
Automatic Bypass-To-Drive or
Drive-To-Bypass Selection
Setup
T12
PID Parameter Settings
Setup
P
0.01
ON
0
32767
I
0.01
ON
0
32767
D
0
ON
0
32767
D Gain
0
ON
0
32767
T13
4-Step Variable Speed
(available only when T8=2)
Setup
Speed 1
10
ON
0
Rated
Frequency
Speed 2
20
ON
0
Rated
Frequency
Speed 3
30
ON
0
Rated
Frequency
Speed 4
40
ON
0
Rated
Frequency
(1) ON: Can be modified at any time. OFF: Drive must be off to modify.