Change time/date/regional settings – Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Commissioning Manual User Manual
Page 65

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
65
Commissioning
Chapter 3
Change Time/Date/Regional Settings
1.
In Windows ME, press Terminal Settings [F4].
2.
Press the Down Arrow to choose
Time/Date/Regional Settings, and press
Enter
.
3.
Choose
Time zone and press Enter.
4.
Scroll up or down and select the desired time zone.
a. Press Daylight Savings [F1]
b. Select the Yes radio button, and press Close [F8].
5.
Press OK [F7].
6.
Choose
Date and press Enter.
a. Press Year [F1], Month [F2], and Day [F3] to set the correct date.
b. Press OK [F7].
7.
Choose
Time and press Enter.
a. Press Hour [F1], Minute [F2], and Seconds [F3] to set the correct
time.
b. Press OK [F7].
8.
Press Close [F8] twice, Reset [F7], and Yes [F7] to restart the HMI.
9.
Select language and bypass mode in the System Parameters Settings
interface.
10.
Press
to accept and proceed to the Main Interface Screen.
Verify the date and time is updated under Version Info.
IMPORTANT
Enter the Time Zone settings before changing the date and time.