Switch Control Sources
Relevant parameter: P4
Description: P4 selects the control source to start, stop, or reset the drive.
There are two Control Sources, the HMI and the hard-wired I/O interface
(DCS). They cannot be enabled at the same time.
Rated/Maximum Output Frequency
Relevant parameter: P460, P466
Description: sets the rated output frequency.
Instruction: P460 is drive’s rated output frequency, which should be the same as
the motor’s rated frequency (0…75 Hz). P466 is the drive’s Maximum Output
Frequency; P460 cannot exceed P466.
Motor Parameter Setting
Relevant parameter: P17, P199
Description: set basic motor parameters, such as rated current and the number of
pole pairs.
Instruction: P199 is motor rated current, which is used to determine faults. P17
sets the number of motor pole pairs.
Hall Effect Current Sensor Setting
Relevant parameter: P198
Instruction: Set the HECS rated current (A) used for the drive current sampling.