Connect dc power – Rockwell Automation 6181P_F VersaView 6181P Integrated Display Computers Install User Manual

Page 15

Advertising
background image

Integrated Display Computers 15

Publication 6181P-IN001I-EN-P - July 2008

Connect DC Power

The 1200P computers with an integrated 24V DC power supply support these
electrical ratings:

18 to 32V DC (24V DC nominal)

6.3 A at 24V DC

The power supply is internally protected against reverse polarity.

1. Secure the DC power wires to the terminal block screws.

2. Secure the ground wire to the GND terminal screw.

3. Apply 24V DC power to the terminal.

ATTENTION

Use a Class 2/SELV (Safety Extra-Low Voltage) isolated and ungrounded power supply as
input power to the workstation. This power source provides protection so that under
normal and single fault conditions, the voltage between the conductors and Functional
Earth/Protective Earth does not exceed a safe value.

ATTENTION

Connect the product to earth ground using a 1.31 mm

2

(16 AWG) or larger external wire.

The ground wire should have green insulation with a yellow stripe for easy identification.

V- (DC Negative)

V+ (DC Positive)

GND (Safety Ground Alternate Connection)

V

-

V+

GND

(Safety Ground)