Environment and Enclosure Information

Review the information on enclosures and environments before installing the
product.

ATTENTION

Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial environment, in
overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes
up to 2000 meters without derating.

This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR Publication 11. Without appropriate precautions, there may be potential
difficulties ensuring electromagnetic compatibility in other environments due to
conducted as well as radiated disturbance.

This equipment is supplied as open type equipment. UL Listed equipment need not be
mounted inside another enclosure if NEMA Type,

UL, or IEC ratings are not required, but the mounting method must limit the tilt of the
product to +/- 30 degrees from vertical. Examples include articulated arm, table-top
stand, wall mount or other means having sufficient mechanical stability and which is
secured to the mounting surface. Units that are not rack-mount ship with a gasketed
bezel to meet specified NEMA Type, UL, and IEC ratings only when mounted in an
enclosure with equivalent ratings. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings required to comply with
certain product safety certifications.

In addition to this publication, see:

Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley

publication 1770-4.1, for additional installation requirements.

NEMA Standards publication 250 and IEC publication 60529, as applicable,

for explanations of the degrees of protection provided by different types
of enclosure.