Devicenet panelview terminals – Rockwell Automation 2711-K9A10_K9C10_T9A10_T9C10 DeviceNet Communications User Guide User Manual

Page 3

Advertising
background image

3

Publication 2711-6.0.4

DeviceNet PanelView
Terminals

DeviceNet terminals have a 10 at the end of their catalog number, for example
2711-K9A10. DeviceNet terminals have

DeviceNet communications port

RS-232 port

Making DeviceNet Connections

Use one of the cables below to connect the DeviceNet version of the PanelView
terminal to a DeviceNet network.

Important: Refer to DeviceNet Cable System Planning and Installation manual

(Publication 1485-6.7.1) for network layout and design information.

DeviceNet Connector

The DeviceNet connector is identified by the label on the PanelView terminal.

The typical DeviceNet current draw is 90 mA at 24V per terminal.

Cable

Catalog No.

DeviceNet Cable, 50 meters (164 feet)

1485C-P1A50

DeviceNet Cable, 100 meters (328 feet)

1485C-P1A150

DeviceNet Cable, 150 meters (492 feet)

1485C-P1A300

DeviceNet

Terminal Block

Terminal

Signal

Function

Color

1

COM

Common

Black

2

CAN_L

Signal Low

Blue

3

SHIELD

Shield

Uninsulated

4

CAN_H

Signal High

White

5

VDC+

Power Supply

Red

1

5

DeviceNet Port