Modifying DeviceNet
Settings from the
Terminal

You can display or modify DeviceNet settings directly from the PanelView
terminal. From the terminal’s Configuration Mode menu, select Communication
Setup.

Restart Terminal [F1]

Resets the terminal.

New Node Address [F2]

Opens the numeric entry scratchpad. Enter the node address (0 - 63) of the
PanelView terminal on the DeviceNet link and press the Enter

key (on touch

screen terminals, press the Enter key on the scratchpad). A node change takes
effect on reset.

Active Node Address

Displays the current network operating address of the PanelView terminal.
Default is 63.

New Baud [F3]

Step through baud rates with each key press: 125K (default), 250K, 500K. The
selected baud rate takes effect immediately.

!

ATTENTION: Settings downloaded with a
DeviceNet application have priority over terminal
settings and take effect immediately after the
download.