Active Baud

Displays the current baud rate of the PanelView terminal. The baud
rate is set to the New Baud value at power-up.

The active baud is the rate of the PanelView, not the network. The
PanelView is not automatically set to the network baud rate.

Bus-off Interrupt [F4]

Specifies what occurs when a CAN bus-off interrupt occurs on the
DeviceNet network.

Hold in Reset holds the PanelView and waits for a
communications reset or a terminal reset. The PanelView is not
allowed network access when Hold in Reset is selected and a
Bus-off Interrupt occurs.

Reset and Continue Communications resets DeviceNet
communications and attempts to re-establish the communications
link.

Interscan Delay [F5]

Provides a delay between scans of the Explicit-Client tags. The
numeric entry scratchpad.Enter a value of 0 to 65535 milliseconds.
This time delay is inserted between each full scan of the Explicit-
Client tags in the current screen context. The value is initially set by
the downloaded application but can be changed by an operator. When
changed, the new value takes effect immediately.

Input Size

Displays the number of words (0 to 64) sent by the PanelView in an I/
O message. 0 is the default value which indicates that no input data is
exchanged with the scanner. This value is set by the downloaded
application.

Output Size

Displays the number of words (0 to 64) received by the PanelView in
an I/O message. 0 is the default value which indicates that no output
data is exchanged with the scanner. This value is set by the
downloaded application.

Comm LED

solid fill - normal operating state

blinking - no communications established

no fill - hardware failure

Exit [F10] or [F16]

Returns to the Configuration Mode menu.