Follow this procedure to install the door.

1. Position the door over the unit opening while holding the right side of the

door slightly toward you and push in the left side until it is flush with the
front of the structure.

2. Swing the door open and slide each hinge pin through the door and

structure hinges.

For Units With

Follow This Step

A control station

First slide the hinge pin through the tab on the control station wiring, then into the
closest hinge.

ArcShield units with 100 ms arc
duration rating

Two hinges are required for each hinge leaf.
1. The upper hinge on each door must be removed from the structure to install/

remove the uppermost hinge pin.

2. Insert the hinge pin through the upper hinge, then through the hinge leaf and

lower hinge.

3. Install the upper hinge on the MCC structure with the 1/4-20 self-tapping screw

provided and tighten to 55 lb•in (6 N•m) with a 3/8 in. socket wrench.

Only top hinge must
be removed to install
hinge pin.

Hinge
Hinge Pin
Hinge Leaf

Hinge for Standard Units and ArcShield Units with Device Limited Rating

Hinge for ArcShield Units with 100 ms Arc Duration Rating

Advertising