Rockwell Automation 2100 CENTERLINE Motor Control Center (MCC) Units with Vertical Operating Handles User Manual

Page 7

Advertising
background image

Rockwell Automation Publication 2100-IN014F-EN-P - March 2014

7

CENTERLINE 2100 Motor Control Center (MCC) Units with Vertical Operating Handles

9. Secure the support pan.

See additional instructions in the table.

Non ArcShield Unit Support Pan Installation

ArcShield Unit Support Pan Installation

10. Replace the isolation barrier if one was removed.

For

Follow This Step

Non ArcShield units

Insert the white plastic retaining clip through the holes in the vertical
wireway wall and pan, working from inside the vertical wireway as shown.
See

Non ArcShield Unit Support Pan Installation

.

All ArcShield units

Secure the unit support pan to the right-hand unit support with the 1/4-
20 self-tapping screw supplied with the bracket and tighten to 55 lb•in (6
N•m) with a 3/8 in. socket wrench. See

ArcShield Unit Support Pan

Installation

.

ArcShield units with 100 ms arc
duration rating

Secure the left-rear corner of the unit support pan with a 10-32 self-
tapping screw and tighten to 32 lb•in (3.6 N•m) using a 5/16 in. socket
wrench.

Plastic Retaining
Clip

Unit Support Pan

Unit Support Pan
Screw

Arc Resistant
Latch
Bracket

Arc
Resistant
Latch
Bracket
Screw

Unit Support Pan

Isolation
Barrier

Advertising