Rockwell Automation 2100 CENTERLINE Motor Control Center (MCC) Units with Vertical Operating Handles User Manual
Page 7
 
Rockwell Automation Publication 2100-IN014F-EN-P - March 2014
7
CENTERLINE 2100 Motor Control Center (MCC) Units with Vertical Operating Handles
9. Secure the support pan.
See additional instructions in the table.
Non ArcShield Unit Support Pan Installation
ArcShield Unit Support Pan Installation
10. Replace the isolation barrier if one was removed.
For
Follow This Step
Non ArcShield units
Insert the white plastic retaining clip through the holes in the vertical 
wireway wall and pan, working from inside the vertical wireway as shown. 
See 
Non ArcShield Unit Support Pan Installation
.
All ArcShield units
Secure the unit support pan to the right-hand unit support with the 1/4-
20 self-tapping screw supplied with the bracket and tighten to 55 lb•in (6 
N•m) with a 3/8 in. socket wrench. See 
ArcShield Unit Support Pan
Installation
.
ArcShield units with 100 ms arc 
duration rating
Secure the left-rear corner of the unit support pan with a 10-32 self-
tapping screw and tighten to 32 lb•in (3.6 N•m) using a 5/16 in. socket 
wrench.
Plastic Retaining 
Clip
Unit Support Pan
Unit Support Pan 
Screw
Arc Resistant 
Latch 
Bracket
Arc 
Resistant 
Latch 
Bracket 
Screw
Unit Support Pan
Isolation 
Barrier