Set software parameters – Rockwell Automation 1799-DASCII DeviceNet Serial Interface User Manual

Page 12

Advertising
background image

12 DeviceNet Serial Interface Module

Publication 1799-IN012B-EN-P - July 2008

RS-485 Mode

To operate in RS-485 mode, follow these steps.

1. Connect TRXD+ to pin 9.

2. Connect TRXD- to pin 1.

3. Connect common to pin 5.

The channel automatically operates in RS-485 mode by connecting these
pins.

Set Software Parameters

The 1799-DASCII module is configured by using the EDS parameters as defined in
the EDS Parameters table.

EDS Parameters

Parameter

#

Access

Description

Parameter Choices

Default
Setting

Default
Value

Data
Type

Serial Port Parameters

Serial port
character
framing

1

Get/Set

Defines
number of
data bits, stop
bits, and
parity in data
character
frame.

0 = 7N2
1 = 7E1
2 = 7O1
3 = 8N1
4 = 8N2

5 = 8E1
6 = 8O1
7 = 7E2
8 = 7O2

8N1

3

USINT

Serial port
comm speed

2

Get/Set

Defines baud
rate of serial
port.

0 = 9600
1 = 1200
2 = 2400
3 = 4800

4 = 19.2 k
5 = 38.4 k
6 = 57.6 k
7 = 115.2 k

9600
baud

0

USINT

Serial port
handshaking

3

Get/Set

Enables
RTS/CTS
hardware
handshaking
on serial port.

0 = RTS/CTS disabled
1 = RTS/CTS enabled

Disabled

0

USINT