Configuration Assembly

The 1799-DASCII module supports a configuration assembly as shown below. The
configuration assembly is accessed through the Assembly Object (Class 4) Instance
103. The configuration assembly data size is 22 bytes.

Transmit
record
number

27

Get/Set

The record
number of the
current transmit
data buffer.

0…255

0

0

USINT

Status

28

Get

The Combined
status byte for
the Serial Port
Object. The
Receive Record
object and the
Transmit Record
object.

No status

0

USINT

Autobaud

29

Get/Set

DeviceNet Baud
Rate

0 = fixed baud
rate
1 = Enable
Autobaud

Enable
Autobaud

1

USINT

Byte

Parameter Definition

EDS Parameter

0

ASCII Serial Character Format

1

1

ASCII Serial Comm Speed

2

2

ASCII Hardware Handshake

3

3

ASCII Max Number of Receive Characters

4

4

ASCII Receive Record Start Mode

5

5

ASCII Receive Start Delimiter

6

6

ASCII Receive Record End Mode

7

7

ASCII Receive End Delimiter

8

8, 9

ASCII Receive Message Timeout

9

10

ASCII Receive String Data Type

10

11

ASCII Receive Pad Mode

11

12

ASCII Receive Pad Character

12

13

ASCII Receive Swap Mode

13

Parameter

#

Access

Description

Parameter
Choices

Default
Setting

Default
Value

Data
Type