Rockwell Automation 1799-DASCII DeviceNet Serial Interface User Manual

Page 15

Advertising
background image

DeviceNet Serial Interface Module 15

Publication 1799-IN012B-EN-P - July 2008

DeviceNet
Handshake
mode

14

Get/Set

If enabled,
master must
acknowledge it
is ready for next
new data before
1799-DASCII
module sends
the new data.

0 = Master/Slave
Handshake
1 = Auto Increment
(No handshake)

Auto
Increment

1

USINT

Gateway
produce
assembly
size

15

Get

Total number of
I/O data bytes
that are sent to
the master from
the 1799-DASCII
module. This
should be the RX
size of your
scanner.

4…254

20 bytes of
array data
and 4
header
bytes

24

USINT

Receive
data string

16

Get

Serial data in the
receive buffer.

Any data string

Empty

Null

USINT

Receive
data size

17

Get

Number of
characters in the
Receive data
buffer.

0…250

0

0

USINT

Receive
record
number

18

Get/Set

The Receive
Record Number
sent from the
master.

0…255

0

0

USINT

Parameter

#

Access

Description

Parameter Choices

Default
Setting

Default
Value

Data
Type