Rockwell Automation 1799-DASCII DeviceNet Serial Interface User Manual
Page 15
![background image](/manuals/580679/15/background.png)
DeviceNet Serial Interface Module 15
Publication 1799-IN012B-EN-P - July 2008
DeviceNet
Handshake
mode
14
Get/Set
If enabled,
master must
acknowledge it
is ready for next
new data before
1799-DASCII
module sends
the new data.
0 = Master/Slave
Handshake
1 = Auto Increment
(No handshake)
Auto
Increment
1
USINT
Gateway
produce
assembly
size
15
Get
Total number of
I/O data bytes
that are sent to
the master from
the 1799-DASCII
module. This
should be the RX
size of your
scanner.
4…254
20 bytes of
array data
and 4
header
bytes
24
USINT
Receive
data string
16
Get
Serial data in the
receive buffer.
Any data string
Empty
Null
USINT
Receive
data size
17
Get
Number of
characters in the
Receive data
buffer.
0…250
0
0
USINT
Receive
record
number
18
Get/Set
The Receive
Record Number
sent from the
master.
0…255
0
0
USINT
Parameter
#
Access
Description
Parameter Choices
Default
Setting
Default
Value
Data
Type