Controlnet application report, Panelbuilder error messages – Rockwell Automation 2711 ControlNet Communications User Guide User Manual

Page 14

Advertising
background image

ControlNet Communications

14

Publication 2711-6.10

The application printout for ControlNet provides the following
information:

configuration data

tag data

The following table lists error messages and codes specific to
ControlNet communications. For all other messages, refer to the
PanelView and PanelBuilder user manuals.

PanelBuilder Tag Error Messages

Message

Recommended Action / Notes

<Tag Name> – Not a ControlNet address tag.

Correct and save the tag in the Tag Form Dialog.

<Tag Name> – Array size (<Value>) is invalid.
You must enter a value between 1 and N.

N will have a value of 128 or 84 depending on the
address type used for the array.

<Tag Name> – Node Name address matches the terminal node address.

Correct value in the Tag Form Dialog.

<Tag Name> – Tag node not configured as a ControlNet node.

Configure the network node in the Communications
Setup Dialog

<Tag Name> – Data may not be consistent with tag.

Tags referencing different data types cannot be grouped.

Tags referencing different network nodes cannot be
grouped.

Tags referencing different data files cannot be grouped.

Tag separation too large for group definition.

<Tag Name> – Data may not be consistent with tag <Tag Name>

Multiple write tags cannot be grouped. In ”Alarm
Setup...”, correct the alarm trigger tag and corresponding
alarm callout tags to remove the error condition.

The 2

nd

<Tag Name> in each error message is the alarm

trigger tag which determines the properties of the tag
group to which the corresponding alarm callout tags must
adhere.

<Tag Name> – Illegal I/O reference.

The tag must be removed from all uses in the
application.

<Tag Name> – Illegal timer/counter read operation.

<Tag Name> – Illegal write to timer status bits.

<Tag Name> - References beyond maximum data file size of 999 elements.

The use of the tag must be changed in the application
editor.

PanelBuilder Node Error Messages

Message

Recommended Action / Notes

<Device Name> – Not configured as a ControlNet node.

Configure the node in the Communications Setup Dialog.

<Device Name> – No InterScan delay assigned, default to 100 ms.

<Device Name> – InterScan delay (<Value> ms) is invalid.
You must enter a value between 100 ms and 1000 ms.

Correct value in the Communications Setup Dialog.

ControlNet
Application Report

PanelBuilder Error
Messages

Advertising