Modifying controlnet settings from the terminal – Rockwell Automation 2711 ControlNet Communications User Guide User Manual

Page 6

Advertising
background image

ControlNet Communications

6

Publication 2711-6.10

The PanelView terminal displays ControlNet settings and allows
changes to the the Node Address and Interscan Delay. From the
Configuration Mode menu of the terminal, select Communication
Setup. The screen below appears.

!

ATTENTION: Settings downloaded with a
ControlNet application have priority over terminal
settings. ControlNet settings take effect immediately
after an application is downloaded.

PV600 Screen Shown

Other Types Similar

New Node Address [F2]

Select the New Node Address field to open the numeric entry
scratchpad. Enter the node addresss of the PanelView terminal
(01 to 99) and press the enter key (on touch screen terminals, press
the enter key on the scratchpad). A change to the node address takes
effect after the terminal is reset. Note: If you enter a value greater
than the UMAX node address, the PanelView will not go online with
the network.

Active Node Address

Read only field displays the current address of the PanelView
terminal.

Interscan Delay [F3]

Displays the current Interscan delay in milliseconds. Select the
Interscan Delay field to open the numeric entry scratchpad. Enter
the delay (100 to 1000 milliseconds in multiples of 10) and press the
enter key (on touch screen terminals, press the enter key on the
scratchpad). A change takes effect immediately.

FW Revision

Displays the currently loaded ControlNet firmware revision.

Modifying ControlNet
Settings from the Terminal