Rockwell Automation AutoMax Enhanced Ladder Language Reference Manual User Manual
Page 238

10Ć36
10.6
About the State of the Unary Array, MultiĆArray, and
Array Compare Instruction Outputs under Various
Input Conditions
The following shows the state of each array instruction output under various input
conditions.
Input Conditions
Output Conditions
EN
instruction's state
DN
ER
Q
ENO
true
initial scan
false
false
false
true
false disabled
false
false
false
false
true
rising edge: error latching the inputs and outputs
true
true
false
false
true
rising edge: inputs are latched
false
false
false
true
true
instruction is executing
false
false
false
true
true
the operation is complete with an error
true
true
false
false
true
the operation is complete and errorĆfree
true
false
true
true
The AR1 and AR2 instructions do not stop on an arithmetic error. They correct the error,
and the operation continues until it is completed. If multiple errors occur, the first error
is logged and the value pointing to where the error occurred is placed into the Index
output when the instruction has completed.
The ARC instruction does not have an ER output. Errors occur during the initial scan,
setting the DN on.