Web server configuration – Rockwell Automation 2711P-xxxx PanelView Plus 6 Terminals User Manual User Manual
Page 108
108
Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013
Chapter 4
Windows CE Operating System
Web Server Configuration
The Web Server tab in the Network Server Configuration dialog box configures 
settings that are used for HTTP web activities. These are standard Microsoft 
Windows CE parameters.
TIP
Always click OK to apply new settings. You are asked if you want to restart the 
service immediately.
Table 54 - Web Server Parameters
Parameter
Description
Default
Admin Users
Specifies a list of users allowed to administer web 
activities. 
When selected, you can enter a list of user names, 
separated by semicolons, in the field that opens at the 
bottom of the dialog box.
ADMIN
Basic Authentication
Check this option to require a user name and password to 
access the web server.
Disabled (unchecked)
Default Web Page
Specifies default web pages users can access.
default.htm;index.htm
Allow Directory Browsing
Check this option to let users browse directories on a web 
server. 
Disabled (unchecked)
Max Connections
Specifies the maximum number of incoming web 
connections.
256
Log File Directory
Specifies the path where the log file is stored. This file logs 
web activity. 
\windows\www
Max Log Size
Specifies the maximum size of the log file stored in the log 
file directory.
A new log file is created, when the current log file reaches 
the maximum size. 
32768 bytes
NTLM Authentication
Check this option to require a valid user name and 
password to access the web server.
If NTLM Authentication is enabled, you must enter a valid 
user name in the Admin Users field. 
NTLM user accounts are defined in the User Account 
Manager of the control panel.
Enabled (checked)