Selecting an enclosure, Backlight considerations, Orientation of the terminal – Rockwell Automation 2711P-xxxx PanelView Plus 6 Terminals User Manual User Manual
Page 178
178
Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013
Appendix B
Outdoor Installations for High-bright Displays
Selecting an Enclosure
http://www.hoffmanonline.com
.
Stirring fans or active cooling be required in high altitude and high ambient 
temperature locations to keep the internal enclosure temperature below 
55 °C (131 °F). Use a heater in installations where the ambient temperature is 
below 0 °C (32 °F). 
Backlight Considerations
The backlight of the high-bright display generates a significant amount of heat 
when set to full intensity. To minimize the amount of heat generated and extend 
the life of the backlight, decrease the display intensity by using the screen saver 
with a 5…10 minute delay.
Orientation of the Terminal
If outside, avoid placing the terminal on the south (north in the southern 
hemisphere) or west side of a cabinet, if possible. This reduces the heat rise due to 
solar loading during the hottest part of the day. 
Mount the terminal vertically to minimize solar loading on the display. Do not 
mount the terminal in a sloped enclosure if it is exposed to direct sunlight.