Check the Start-up Messages and Codes
Refer to Start-up Messages and Codes on page 164
for a list of message states and
error codes that can appear on the splash screen during startup.
Check Voltages and Temperatures
Check the battery voltage, processor temperature, and display temperature.
Check the System Event Log
Check the system event log for errors or unexpected behaviors:
• From FactoryTalk View ME Station Configuration mode, press Terminal
Settings>System Event Log. Refer to
View and Clear the System Event
• From the control panel, open the Hardware Monitor and click the System
Event Log tab. Refer to
Table 79 - Checking Voltage and Temperature Conditions
Check for These Conditions
Where
What to Do
Battery voltage
< 2.75V DC
• From terminal desktop: Refer
• From FactoryTalk View ME Station
Configuration mode:
Refer to
Replace the battery if needed.
CPU temperature
>95 °C (203 °F)
• From terminal desktop: Refer
• From FactoryTalk View ME Station
Configuration mode:
Refer to
Check for obstructed airflow in
the chassis and attempt to
moderate the ambient
temperatures within the
enclosure and surroundings.
Display temperature
>55 °C (131 °F)
• From terminal desktop: Refer
:
• From FactoryTalk View ME Station
Configuration mode:
Refer to