Dh-485 network port wiring – Rockwell Automation 2711P-xxxx PanelView Plus 6 Terminals User Manual User Manual
Page 146

146
Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013
Chapter 6
Terminal Connections
DH-485 Network Port Wiring
Refer to the figures to attach the RS-485 connector to a Belden 3106A or 9842
cable.
Refer to Controller Connections on page 151
if you are using standard
Allen-Bradley
®
cables.
Figure 20 - Daisy-chain Connection
Attach the connector to a Belden 3106A or 9842 cable as shown in
Figure 21
or
Figure 22
.
Figure 21 - Single Cable Connection
Figure 22 - Multiple Cable Connection
IMPORTANT
A daisy-chained network is recommended. We do not recommend a hybrid
star/daisy chain networks as shown.
Table 71 - Belden 3106A Wire Connections
For this Wire/Pair
Connect this Wire
To this Terminal
Shield/Drain
Non-jacketed
Terminal 2 - Shield
Blue
Blue
Terminal 3 - (Common)
White/Orange
White with Orange Stripe
Terminal 4 - (Data B)
Orange with White Stripe
Terminal 5 - (Data A)
Belden
#3106A or
#9842
Belden
#3106A or
#9842
Belden
#3106A or
#9842
Connector
Connector
Connector
Incorrect
Orange with White Stripes
White with Orange Stripes
Shrink Tubing
Recommended
Blue (#3106A) or
Blue with White Stripes (#9842)
Drain Wire
6 Terminal
5 A
4 B
3 Common
2 Shield
1 Chassis Ground
to Previous Device
to Successive Device