Example CNXOR.CFG File (continued)

############################################

# Define the Connections we will be using.

#

Connection.name: mr rackio rackin rackout

#

# Describe the connections.

#

# default values for those not specified

Connection.default.timeout: 0A

Connection.default.epr: 0E71

# 5ms epr

Connection.default.net_t_o: 0000

Connection.default.net_o_t: 0000

Connection.default.transport: 01

# Message Router parameters.

Connection.mr.title: Message Router

Connection.mr.max_instance: 1

Connection.mr.epr:

2BD0

# 1 second epr

Connection.mr.net_t_o: 43ff

Connection.mr.net_o_t: 43ff

Connection.mr.transport: A3

Connection.mr.class: 02

# Input Rack parameters.

Connection.rackin.title: Input Rack

Connection.rackin.max_instance: 1

Connection.rackin.net_t_o: 281A

Connection.rackin.class: 7C

Connection.rackin.transport: 81

Connection.rackin.path: 2c 01 80 05 01 00 0c 00 18 00 01 01 02 00

# Output Rack parameters.

Connection.rackout.title: Output Rack

Connection.rackout.max_instance: 1

Connection.rackout.net_o_t: 4816

# 16 slot, single density

Connection.rackout.class: 7C

Connection.rackout.transport: 01

Connection.rackout.path: 2c 02 80 04 01 00 0c 00 18 00 01 01

Connection.rackout.1stmsg:

rout1

# Output/Input Rack parameters.

Connection.rackio.title: I/O Rack

Connection.rackio.max_instance: 1

Connection.rackio.net_t_o: 281A

#Connection.rackio.net_o_t: 4816 # 16 slot, single density

Connection.rackio.net_o_t: 480A

# 4 slot, single density

Connection.rackio.class: 7C

Connection.rackio.transport: 01

Connection.rackio.path:

2c 02 2c 01 80 05 01 00 0c 00 18 00 01 01 02 00

Connection.rackio.1stmsg:

rout1