AN-T80004 Field Loop Configuration

Issue 10 Jun 13

AN-T80004

16

Digital Inputs

Thresholds

Digital inputs are essentially analogue inputs which are interpreted as digital. The voltage on the input
circuit is measured and allocated to an input state using thresholds, similar to analogue inputs above.
For digital inputs, the state bands are essential, since they define the digital input ‘off/open’ and
‘on/closed’ as well as line fault status. The thresholds are similar to analogue inputs except that they
operate over a wider voltage range. There are five configurable states separated by pairs of thresholds
for rising and falling state change. There are no THRSHIN and THRSHOUT boards to change the
thresholds online.

Typical
voltage
threshold
values

Input
Channel
State


DI
Status


Line
Fault
Status

Over-range

7

False

True

Tmax 36.00

False

True

Short Circuit (approx 24V)

5

T8 22.00

4 or 5

False /

False /

T7 21.00

True

True

Contact Closed (approx 16V)

4

True

False

T6 12.75

3 or 4

False /

False /

T5 12.25

True

True

Contact Indeterminate

3

False

True

T4 11.75

2 or 3

False /

T3 11.25

True

Contact Open (approx 8V)

2

False

False

T2 3.00

1 or 2

False /

T1 2.00

True

Open Circuit (approx 0V)

1

False

True

Tmin -8.00

Under-range

7

False

True

Thresholds are defined using a threshold template in the system configuration. Product description PD-
8082 describes how to edit threshold templates. The example above shows ‘Closed’ defined at
nominally 16 volts and ‘Open’ at nominally 8 volts, for a 24V digital input module. These are spaced
equally through the input voltage range, which allows broad voltage bands for each state.