AN-T80004 Field Loop Configuration

Issue 10 Jun 13

AN-T80004

43

Other Issues

System Cable Design

The diagrams below show how to wire the system I/O cables and power supplies for each type of
termination and cable design. Cable choices are shown in the cable PDs TC-200, TC-500, TC-600 and
TC-700.

‘Internal’ cables are protected with a nylon braid and are suitable for use inside a single panel.
‘External’ cables have a sheath but are not armoured and are suitable for routing within a building but
not in trenches.

Analogue or Digital Input module to FTA

Wire the 24V supplies through 3A fuses; the T8193 is designed for this.

FTA

5

TB1

4 3 2 1

Module

24V A

24V B

0V

To Screen Earth

To Safety Earth