Trusted – Rockwell Automation T80004 Application Note Field Loop Configuration User Manual

Page 44

Advertising
background image

Trusted

TM

AN-T80004 Field Loop Configuration

Issue 10 Jun 13

AN-T80004

44

Analogue or Digital Input module to VFTA

The T8842 VFTA has five power supply plugs. Each plug powers one ‘power group’ of eight channels
(see page 27). For field devices that require only milliamps to drive the loop current, only one dual 3A
supply is needed and the plugs should be linked together. For field devices that require more current,
each plug may be wired from a dual 3A supply. If 3A is not enough for eight channels, fit separate 24V
and 0V fused terminals for each channel. The diagram below shows only one 3A dual supply for low
current devices, with wire links between the terminals.

VFTA

TBFP1 1 2 3 4

Module

24V A

24V B

0V

TBFP4 1 2 3 4

TBFP3 1 2 3 4

TBFP5 1 2 3 4

TBFP2 1 2 3 4

To Screen Earth

To Safety Earth