AN-T80004 Field Loop Configuration

Issue 10 Jun 13

AN-T80004

51

Cable earth and screen wires

At either end of an I/O cable there may be a braid or heavy gauge green or green/yellow cable. This is
the protective earth and should be bolted to safety earth. The chassis have a row of threaded holes for
terminating these braids.

On some I/O cables there may be a thin green wire. This is a screen earth and should be wired to a
separate terminal, connected to a clean reference earth separate from safety earths.

24V

Channel

0V

250R

250R nominal

Channel
output

0V

Channel
output

0V

250R nominal