AN-T80020 Diagnostics Procedure

Issue 12 Feb 11

AN-T80020

32

Main Processor System Logs

MON 2009-03-23

17:02:56 25 Cfg: Configuration file loaded.

17:02:56 26 IMB: LRAM power up test passed

17:02:59 51 ISaGRAF: Create Comms space (req=1024, max=1024)

17:03:06 22 A/S: Processor mode set to Active

17:03:06 26 IMB: Expander configuration complete

17:03:06 26 IMB: Found CI module - Chassis 1 Slot 7

17:03:06 28 IMB: Slave connection manager started - Chassis 1 Slot 7

17:03:06 33 NIO: Found TMR 24Vdc Digital Input - Chassis 1 Slot 1

17:03:06 33 NIO: Found TMR Analogue Input - Chassis 1 Slot 3

These logs show date-stamps at the start of each day (e.g.

MON 2009-03-23

above). Each entry has a

time stamp, the number and name of the task that wrote the entry (e.g.

26 IMB:

) and a text description

of the entry. Most entries will be due to normal operation. To find the current state of the system, read
the log from the bottom, up to the first ‘fault reset’ entry. Some possible entries are shown below.

NIO: Disabling interface (Rack 1 Slot

5), slice C

A module slice is being set offline by the processor;
this will appear in the I/O module as an 0x8741 fault.
Check the First-Line Diagnostics advice for a steady
red I/O module 'Healthy' LED

NIO: CLI error (FAIL) - Chassis 3 Slot 7

Slice C

The I/O module slice has stopped communicating

NIO: Lost (Rack 3 Slot 1) …

A module has been removed

NIO: Simulating …

The system is running without the module

NIO: Module(s)

removed/unconfigured/simulated

The processor is warning that it is still running without
all modules

IMB: Expander FCR fault set - …

Communications via expander modules has failed

NIO: Channel 6 Discrepancy (Rack 6 Slot

5), slice C

I/O point measurement discrepancy; this will appear in
the I/O module as a 0x70nn fault. Check the First-Line
Diagnostics advice for a flashing red I/O module
'Healthy' LED

CLI Response Error FAIL - Chassis 2 Slot

11

A module is missing on startup

FPS: [Manual] System fault reset

The reset pushbutton has been pressed

NIO: Linked (or) Unlinked Chassis 3 Slot

7 - Chassis 3 Slot 12

Two I/O modules have been partnered for a hot swap
(linked) or the partnership has been broken (unlinked)

NIO: Impending module removal set (or)

cleared - Chassis 2 Slot 9

The ejector tabs on this module have been opened (or)
closed. If the log reports alternating set/cleared
messages, the ejector switches are faulty.

NIO: Slice fault - Chassis 4 Slot 9

A module has a fault but is still running. Check the
First-Line Diagnostics advice for a flashing red I/O
module 'Healthy' LED

NIO: Module not properly configured -

Chassis 3 Slot 2

The I/O module has rejected its System.INI
configuration. It will have shut down on starting the
system.

NIO: Illegal 'standby' module state

(fatal) - Chassis 4 Slot 1

The I/O module was set Active but went back to
Standby. This probably indicates that it has rejected its
System.INI configuration.

IMB: Permanent minor fault (MBCU)

Chassis 4 Slot 13 FCR C

Indicates a permanent problem with system
communication to the given chassis, slot and slice.