AN-T80020 Diagnostics Procedure
Issue 12 Feb 11
AN-T80020
48
0x3000 Series Codes (Field Interface ASIC)
FIA_INVALID_IMAGE
0x3000
Modules:All
This test checks the application firmware in FLASH on loading the Field
Interface firmware. Detects a FLASH memory fault or missing
firmware. The module will stay in boot mode. Return the module for
repair.
Action:Slice will not boot
FIA_INVALID_IMAGE_CRC
0x3001
Modules:All
This test performs a CRC check on the firmware in FLASH on loading
the Field Interface firmware. Detects a FLASH memory fault or
corrupted firmware. The module will stay in boot mode. Return the
module for repair.
Action:Slice will not boot
FIA_CONFIGURE_ERROR
0x3002
Modules:All
The field interface adapter controllers couldn’t be initialized. The
module will stay in boot mode. Return the module for repair.
Action:Slice will not boot
FIA_NOT_PRESENT
0x3003
Modules:All
The field interface adapter did not respond when turned on. The
module will stay in boot mode. Return the module for repair.
Action:Slice will not boot
FIA_POWERUP_ERROR
0x3004
Modules:All
The field interface adapter did not draw the expected current when
turned on. The module will stay in boot mode. Return the module for
repair.
Action:Slice will not boot
FIA_CONFIGURE_TIMEOUT
0x3005
Modules:All
The field interface adapter controllers’ initialization took too long. The
module will stay in boot mode. Return the module for repair.
Action:Slice will not boot
FIA_HIA_SYNC_FAULT
0x3006
Modules:BOOT CODE
Synchronisation fault on the Host Interface adapter. Return the module
for repair.
Action:Slice fault
FIA_FIA_SYNC_FAULT
0x3007
Modules:BOOT CODE
Synchronisation fault on the Field Interface adapter. Return the module
for repair.
Action:Slice fault
FIA_CHANNEL_FAULT
0x31nn
Subcode:nn = output channel
0x01 to 0x28 (1 to 40)
Modules:8480
Detects a faulty channel on the field interface adapter (see also
0x52nn)
Swap the module and test it in an unused unconnected slot. If it still
indicates the same fault, return the module for repair. If its replacement
has the same fault, check the field circuits and earthing.
Action:Slice fault