4-2

Using the SP120 AC Drive Demo Unit

Step 9. Press and hold PROGram,

,

, and

for 3 seconds.

Step 10. Release only. Hold the other keys down until the

display starts to blink, then release the remaining
keys.

d01 will be displayed when the defaults have been
successfully restored.

Lab B: Set up the drive for local (keypad) operation
using the following procedure:

Tools required: None

Step 1. Use the PROGram and

▲ ▼

keys to select the F

parameter group.

Step 2. Set F02 [

ACCEL

TIME

] to 3.0 sec.

Step 3. Set F03 [

DECEL

TIME

] to 3.0 sec.

Step 4. Set A01 [

FREQUENCY

COMMAND

SELECT

] to 00. This

selects the drive’s speed pot as the frequency
source.

Step 5. Set A02 [

START

COMMAND

SELECT

] to 02. This

selects the input from the Start key ( ) on the drive
keypad.

Step 6. Verify that A03 [

BASE

FREQUENCY

] and A04

[

MAXIMUM

FREQUENCY

] are set to 60hz.

Step 7. Set A82 [

BASE

VOLTAGE

] to 230V.

Step 8. Set b12 [

MOTOR

OVERLOAD

CURRENT

] to 0.60 amp.

Step 9. After you have set the above parameters, press

. You should now be able to vary the speed of the
motor using the speed pot on the drive.

The

CONF

OUT

indicator lamp turns on when the

requested frequency is reached.

Notice that the

RUN

LED

is on to indicate the drive is

responding to the start command.

The

LED

s above and the speed pot are on to

indicate they are active.

Step 10. Press to stop the drive.