Advise tags and Polled tags use Location4 to specify the requested
update rate for the group.

Location4 is ignored for Output tags.

NOTE

Advise, Polled, and Output data collection methods are explained in
"Location3 (page 25)".

If

Location5=1 and Location3=0, it will force an asynchronous read

from the data server. It should only be used for event-triggered
points due to performance concerns.

The InstrumentTag contains the ItemID of the tag. The format of
this field depends on the FactoryTalk Live Data server:

Type of the tag InstrumentTag syntax

Device tags

<application name>/<area name>:<data server
name>:[<shortcut name>]<tag name>

HMI tags

<application name>/<area name>:<HMI server Name>:<folder
name>\<tag name>

The field must match the point defined on the FactoryTalk Live
Data server, including punctuation, spaces, and case.

The InstrumentTag field allows a maximum of 1023 characters.

The FTLD interface gets the $Global scope from the

/FTDirectory

parameter and

/ from the /FTContext parameter. For additional

information on these parameters, see "Command-line Parameters
(page 39)".

Advise and Polled Tags

Output Tags

Location5

InstrumentTag