Error and informational messages, Chapter 12, Error and informational – Rockwell Automation FactoryTalk Historian SE 4.0 Live Data Interface User Guide User Manual

Page 51: Messages

Advertising
background image


Rockwell Automation Publication HSELD-UM024A-EN-E–September 2013

51

Chapter 12

Error and Informational Messages

The FTLD Interface is based on the PI-UniInt framework,
therefore a few error messages are sent to the PIPC log by PI-UniInt.
Other error messages are sent to the FactoryTalk Diagnostics
system. When troubleshooting, we recommend that you check both
FactoryTalk Diagnostics and the PIPC log.

The following is the list of error messages sent to FactoryTalk
Diagnostics.

Severity

Message text

Error

Failed to disconnect from FactoryTalk.

Error

Failed to initialize COM library.

Error

Failed to initialize COM security.

Error

Missing or invalid interface ID parameter.

Error

Failed to initialize FactoryTalk Diagnostics.

Error

Failed to launch FTLD interface due to the lack of the parameter
/FTDirectory.

Error

Failed to launch FTLD interface due to the lack of the parameter

/FTContext.

Error

Failed to connect to FactoryTalk Directory scope %s.

Error

System error: Insufficient memory.

Warning

Failed to remove FactoryTalk Live Data item <%s>.

Warning

PI point <%s> is refused because of failure to add FactoryTalk Live
Data item <%s>.

Warning

PI point <%s> is refused because of the invalid attribute of
Location [3].

Warning

PI point <%s> is refused because of the invalid attribute of

InstrumentTag.

Warning

PI point <%s> is refused because of the invalid attribute of
Location [4].

Warning

The value quality of PI point <%s (PointID: %d)> with FactoryTalk
Live Data item <%s> is bad.