Monitored Digital Input Modules (T3411)
 
1 4  
Industrial Control Services
Line Monitoring
The Monitored digital input module can perform line 
monitoring of the field wiring when a suitable line monitor 
device is installed across the field input switch. Two types of 
line monitor devices are available to match the type of module 
configuration used in the application. 
Figure 8 shows a single switch connected to a single monitored 
input module. This type of configuration uses the T0412 line 
monitor device which contains two resistors, one in series with 
the field switch and one in parallel with the field switch. 
Figure 8 also applies to fault tolerant input configurations 
that include redundant sensors connected to redundant input 
modules. 
Figure 8. Line Monitoring, Single Switch Connected to
Single Module.
For fault tolerant configurations using single sensors 
connected to redundant input modules, the T0413 line 
monitor device is used as shown in Figure 9. This line 
monitor device includes two zener diodes, one in series with 
the field switch and one in parallel with the field switch.