Rockwell Automation T3411 ICS Regent Monitored Digital Input Modules User Manual
Page 25
 
Monitored Digital Input Modules (T3411)
 
P D - 6 0 3 1 M a r - 0 6  
25
Intrinsic Safety
External barrier, if required. 
(requires threshold 
adjustment, see page 18). 
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity, 
non-condensing 
Vibration
10 to 55 Hz:
±0.15mm
Shock
Operating:
15 g, ½ sine wave, 11 msec
Electromagnetic 
Interference 
•
IEC 801 Part 2 - Electrostatic
Discharges
•
IEC 801 Part 3 - Radiated
Electromagnetic Fields
•
IEC 801 Part 4 - Transients
and Bursts
•
ANSI/IEEE C37.90 - Surge
Withstand Capability
 
Level 3: Contact discharge of 
6 kV 
Level 3: 10 V/M, 27 MHz - 
500 MHz 
Level 4: 2 kV, 2.5 kHz for t = 
60 seconds 
2.5 kV damped 1 MHz sine 
wave 
4 kV bi-directional impulse, 
10 nsec rise time, fast 
transient 
Safety
Certified to DIN V VDE 
0801 for Risk Class 5. Also 
designed to meet UL 508 and 
CSA 22.2, No. 142-M1981 
Dimensions 
 
Height:
Width:
Depth:
 
12.6" (320 mm) 
1.27" (32 mm) 
10.12" (257 mm) 
Weight
3.3 lbs (1.5 kg)