Monitored Digital Input Modules (T3411)
 
2 2  
Industrial Control Services
In this example, IN1A and IN1B represent the input 
variables from two redundant monitored input modules. 
IO01U01 and IO01U02 are the system control relays that 
report a fault for the monitored input modules (one installed 
in slot 1 of chassis 1 and the other in slot 1 of chassis 2). The 
variable IN1VOTE is a shared control relay that will 
represent the voted value of the two inputs. This variable 
would be used elsewhere in the application program to 
represent the status of the field input in the associated safety 
interlock logic. 
When both input modules are healthy, both inputs must turn 
off to turn off the voted result and initiate a trip. Because the 
inputs are normally energized, the voted result is normally 
on. If a fault occurs on one of the input modules, the voted 
result will remain on, eliminating a nuisance trip. Automatic 
testing of the input module will detect the fault and the 
associated fault bit will be turned on, leaving the voted result 
under the control of the remaining healthy input module. 
The faulted module can be removed and replaced. After 
replacing the input module and performing a voted reset, the 
fault bit is turned off, restoring the input configuration to the 
dual mode. 
Normally De-Energized Inputs
Figure 15 shows a ladder logic rung that would be suited for 
normally de-energized inputs that energize to trip. 
Figure 15. Dual Voting for Normally De-Energized Inputs.
In this example the variables represent the same status 
information as described above for normally energized inputs. 
When both input modules are healthy, both inputs must turn 
on to turn on the voted result and initiate a trip. Because the 
inputs are normally de-energized, the voted result is normally 
off. If a fault occurs on one of the input modules, the voted