Monitored Digital Input Modules (T3411)
 
8  
Industrial Control Services
Application
Simplex Configuration
Monitored digital input modules provide a suitable interface 
to safety-critical input signals. The circuits in the monitored 
digital input modules are automatically tested and 
annunciated, providing a fail-safe interface to digital inputs. 
This simplex input configuration is illustrated in Figure 3. 
Figure 3. Single Monitored Digital Input Configuration.
Fault Tolerant Configurations
For fault tolerant applications, redundant monitored input 
modules are used in a fault tolerant configuration. In one 
configuration the redundant input modules are connected in 
parallel to a single field input device as illustrated in Figure 
4. If redundant field sensors are installed in the field, the 
modules are connected so that each sensor connects to one of 
the modules as illustrated in Figure 5. In these fault tolerant 
configurations, each monitored digital input module is hot 
replaceable. If a fault occurs on one module, it can be 
removed and replaced while the system continues to correctly 
sense the inputs from the remaining module(s).