Rockwell Automation T3411 ICS Regent Monitored Digital Input Modules User Manual
Page 18
 
Monitored Digital Input Modules (T3411)
 
1 8  
Industrial Control Services
3) Define the Input Module Fields and Thresholds:
With the cursor at the top of the list in the Module 
Definition dialog shown in Figure 11, open the Line 
Monitored Input Module dialog by pressing Enter or 
double clicking on the “(Module)” selection. The dialog box 
shown in Figure 12 will open. 
Figure 12. Defining the Input Module Fields and Thresholds.
In the module definition dialog you can define a tag names 
representing all sixteen input points as a 16-bit word. The 
Name field represents the On/Off status of all sixteen 
inputs and the Fault Name represents the Line Fault 
status of all sixteen inputs. 
The module tag names represents the 16 inputs as a 
signed, 16-bit integer. In this format, input point one is 
the least significant bit (LSB) and input point 16 is the 
most significant bit (MSB). Enter tag names up to 12 
characters long and descriptions up to 40 characters long. 
In the module definition dialog you can also set the 
threshold values used to determine the Open Circuit, 
On/Off, and Short Circuit input status. Normally these 
should be left at the default values of 20, 12 and 4 Vdc 
shown in Figure 12. These values are applicable to field 
inputs with no line monitor device installed and also for