MODBUS Master Package for W

INTERPRET

(T3837)


P D - 6048 August, 96

(Issue 1)

13

The variable parameters are as follows:

Name

The variable to be associated with the specified MODBUS address. This is
a required field and must be a valid Winterpret tag name.

Node

The MODBUS node to be associated with the specified MODBUS
variable. This is a required field and must contain a valid node number in the
range of 1 - 247.

Address

The MODBUS address to be associated with the specified MODBUS
variable. This is a required field and must contain a valid MODBUS
address in the range of 0 - 49,999. This address determines the MODBUS
function to be used.

Usage: Read/Write

The MODBUS function usage: to send data or receive data from a
MODBUS slave. This is a required field and must follow the MODBUS
variable type as implied by the MODBUS address.

Delete Variable

The Delete Variable command allows you to remove the currently selected
variable from the MODBUS Master variable list.

Add Multiple

The Add Multiple command allows you to add a number of MODBUS
variables to the MODBUS Master Function Block Editor window with a
single action. Choosing this command opens the dialog box shown in
Figure 4.