MODBUS Master Package for W

INTERPRET

(T3837)


P D - 6048 August, 96

(Issue 1)

9

Field

Type

Description

E

NABLE

Tag

If specified, must be the name of a valid bit variable.
If not specified, the MODBUS function block is
assumed to always be enabled.

R

ESET

Tag

If specified, must be the name of a valid bit variable.
If not specified, the E

RROR

output can only be

cleared by stopping, and then restarting the
MODBUS function block.

E

RROR

Tag

If specified, must be the name of a valid bit variable.

C

ODE

Tag

If specified, must be the name of a valid word
variable.

N

ODE

Tag

If specified, must be the name of a valid word
variable.

T

IME

Tag

If specified, must be the name of a valid floating
point variable.

T

OGGLE

Tag

If specified, must be the name of a valid bit variable.

A rule violation results in an error message, but the validation procedure
continues until all parameters have been checked. After the parameters are
checked, each variable definition is validated according to the criteria
presented in Table 7.

Table 7 - Variable Definition Validation Rules

Field

Type

Description

Name

Tag

Must be the name of a valid variable. The size and
usage of the variable must match the attributes as
specified by the value of the Address field. (Refer to
Table 8 for additional information.)

Address

Constant

Must be between 0 and 49,999.

Node

Constant

Must be between 1 and 247.

Usage

Switch

Must specify either Read or Write.

Address Range

Regent Type

MODBUS Type

MODBUS Cmd

Usage

0 9999

Bit Variable

Coil

01

Read or Write

10000 19999

Bit Variable

Input

02

Read Only

20000 29999

Reserved

-

-

-

30000 39999

Word Variable

Input Register

04

Read Only

40000 49999

Word Variable

Holding register

03

Read or Write