MODBUS Master Package for W

INTERPRET

(T3837)


P D - 6048 August, 96

(Issue 1)

22

A MOD MASTER type port has the following restrictions:

·

8 data bits

·

2 stop bits and no parity bit, or 1 stop bit and 1 parity bit.


In addition, the Node field is not valid in this context, and is set to zero (0).

Figure 12. Serial Port Settings Dialog Box

Refer to Section 4 of the Regent

Ò

+ Plus User’s Guide for more

information on working with serial ports.