Input isolation transformers might be needed to help eliminate the
following:

·

Damaging line voltage transients from reaching the drive.

·

Line noise from the drive back to the incoming power source.

·

Damaging currents that could develop if a point inside the drive

becomes grounded.

Observe the following guidelines when installing an isolation transformer:

·

A power disconnecting device must be installed between the power line

and primary of the transformer.

·

If the power disconnecting device is a circuit breaker, the circuit breaker

trip rating must be coordinated with the in-rush current (10-12 times full
load current) of the transformer.

Optional isolation transformer

ATTENTION:

Distribution system capacity above the maximum

recommended system KVA requires the use of an isolation transformer,
a line reactor, or other means of adding similar impedance to the drive
power input. Failure to observe these precautions could result in
damage to, or destruction of, the equipment.