Rockwell Automation DC3R Regenerative DC Drive User Guide 1/4 - 2 HP, 115/230 VAC User Manual
Page 19
![background image](/manuals/581209/19/background.png)
11
Installation
Cage-clamp terminal block
Connections to the DC3R drive are made to a cage-clamp terminal block
(Figure 4). To insert a wire into the terminal block, press down on the
lever arm using a small screwdriver. Insert stripped wire into the large
opening in front of the terminal block. Release the lever arm to clamp the
wire.
Lever Arm
Figure 4. Cage-Clamp Terminal Block
Field output
The field output is for shunt wound motors only. Do not make any
connections to F1 and F2 when using a permanent magnet motor.
Use 18 AWG wire to connect the field output to a shunt wound motor.
Table 1 lists the field output connections.
Table 1. Field Output Connections
Line Voltage
Approximate
Connect Motor
(VAC)
Field Voltage (VDC) Field To
115
50
F1 and L1
115
100
F1 and F2
230
100
F1 and L1
230
200
F1 and F2