AC Guarded Digital Output Module (T3464)


2 0

Industrial Control Services

Table 4. Operating Diagnostic Messages.

Display

Description

AC

AC quality problem (i.e. frequency is out of tolerance, frequency
is unstable, or phase difference between output groups 1-8 and
9-16).

AC.ab

AC power failure at field terminals A/B (output group 1-8).

AC.cd

AC power failure at field terminals C/D (output group 9-16).

Shud

Outputs are shut down (off). Caused by the loss of controller
communications or the module is not configured in the system.

Hold

Outputs are held at last state. Caused by the loss of controller
communications.

BFnn

Blown fuse on output nn.

OLnn

Open load on output nn. Displayed only when output is on.

OCnn

Open circuit on output nn. Switch is not able to close.

SCnn

Short circuit on output nn. Switch is not able to open. The
crowbar switch was activated to blow the fuse. Blown fuse
message is suppressed.

Safety Considerations

Although the AC Guarded output modules provide extensive
diagnostics and testing features, they have only been TÜV

certified to Risk Class 5 as non-interfering. For safety
systems that require TÜV approved equipment, the T3484
Monitored Guarded output module is recommended.

Specifications

Safetybus Power

1.5 load units

Number of Inputs

16 circuits divided into two
groups of eight

Voltage Range

90 to 130 VAC

Frequency Range

47 to 63 Hz

Phase Difference

1º maximum between group
1-8 and group 9-16