AC Guarded Digital Output Module (T3464)


2 2

Industrial Control Services

Isolation

2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1-8 to output group
9-16)

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Storage Temperature

-40

°

to 85

°

C

(-40

°

to 185

°

F)

Operating Humidity

0 to 95% relative humidity,
non-condensing

Vibration

10 to 55 Hz:


±0.15mm

Shock

Operating:


15 g, ½ sine wave, 11 msec

Electromagnetic
Interference

IEC 801 Part 2 - Electrostatic

Discharges

IEC 801 Part 3 - Radiated

Electromagnetic Fields

ANSI/IEEE C37.90 - Surge

Withstand Capability


Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz -
500 MHz

1 kV damped 1 MHz sine
wave

Safety

Certified to DIN V VDE
0801 for Risk Class 5, non-
interfering. Also designed to
meet UL 508 and CSA 22.2,
No. 142-M1981

Dimensions

Height:

Width:

Depth:


12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)

Weight

5.0 lbs (2.3 kg)