AC Guarded Digital Output Module (T3464)
2 2
Industrial Control Services
Isolation
2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1-8 to output group
9-16)
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity,
non-condensing
Vibration
10 to 55 Hz:
±0.15mm
Shock
Operating:
15 g, ½ sine wave, 11 msec
Electromagnetic
Interference
•
IEC 801 Part 2 - Electrostatic
Discharges
•
IEC 801 Part 3 - Radiated
Electromagnetic Fields
•
ANSI/IEEE C37.90 - Surge
Withstand Capability
Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz -
500 MHz
1 kV damped 1 MHz sine
wave
Safety
Certified to DIN V VDE
0801 for Risk Class 5, non-
interfering. Also designed to
meet UL 508 and CSA 22.2,
No. 142-M1981
Dimensions
Height:
Width:
Depth:
12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)
Weight
5.0 lbs (2.3 kg)