Testing and diagnostics, Ac guarded digital output module (t3464), Table 1. output states after switch failure – Rockwell Automation T3464 ICS Regent AC Guarded Digital Output Module User Manual

Page 4

Advertising
background image

AC Guarded Digital Output Module (T3464)


4

Industrial Control Services

Table 1. Output States After Switch Failure.


Case

Commanded

Output State

Single

Failure

Actual

Output

to Load


Remarks

1

On

TRIAC

short

On

Continued correct control.
Automatic testing of crowbar
circuit ensures that output will be
able to switch off. If output is
subsequently commanded off,
crowbar switch is energized to
blow fuse and turn off output
(fuse blows 200 msec after
output is commanded off).

2

On

TRIAC

open

Off

Fail-safe output. Automatic
testing detects failed TRIAC.

3

On

Crowbar

fault

On

Continued correct control.
Automatic testing detects failed
crowbar circuit. If output is
subsequently commanded off,
TRIAC will turn off.

4

Off

TRIAC

short

200

msec
bump

A one-time, 200 msec maximum
on-state bump occurs when the
TRIAC shorts. Automatic testing
detects shorted TRIAC and
crowbar switch is activated to
blow fuse. This one-time bump
may not be suitable for certain
energize-to-trip applications.

5

Off

TRIAC

open

Off

Fail-safe output. Automatic
testing detects failed TRIAC. If
output is subsequently
commanded on, output will
remain off.

6

Off

Crowbar

fault

Off

Continued correct control.
Automatic testing detects failed
crowbar circuit. If output is
subsequently commanded on,
TRIAC will turn on.

Testing and Diagnostics

The voter and I/O bus interface logic of the Guarded output
modules is automatically tested by the processor modules.
Discrepant data are sent through one of three legs of the I/O
Safetybus to determine whether the module’s voters are able
to outvote the incorrect data. A failure to return the correct
majority-voted result to the processors produces an I/O